A simple demand-side management solution for a typical compressed-air system at a South African gold mine

Authors

  • Leon Liebenberg University of Cape Town
  • Douglas Velleman
  • Walter Booysen

DOI:

https://doi.org/10.17159/2413-3051/2012/v23i2a3159

Abstract

Once designed, mine compressed-air systems tend to operate at peak levels throughout the life of the mine, despite there being significant periods when this air quantity is not required. This is mainly due to lack of appropriate compressor controls. Consequently, such compressed-air systems are inefficient and wasteful. A compressed-air system at a South African gold mine was retrofitted with an automatic compressor control system featuring compressor cascading and pressure bandwidth control. The goal was to implement a simple demand-side management (DSM) strategy to afford meaningful electrical energy savings. The automatic control strategy realised a saving of 1.25 MW (on a baseline of 7.22 MW) during Eskom’s evening peak demand window. This represents a reduction of 17.3% in electrical power consumption during the evening peak period, and savings of nearly R2.9 million per year.

Downloads

Download data is not yet available.

Metrics

Metrics Loading ...

Author Biography

Leon Liebenberg, University of Cape Town

Energy Research Centre Snr Research Officer

Downloads

Published

2012-05-01

How to Cite

Liebenberg, L., Velleman, D., & Booysen, W. (2012). A simple demand-side management solution for a typical compressed-air system at a South African gold mine. Journal of Energy in Southern Africa, 23(2), 20–29. https://doi.org/10.17159/2413-3051/2012/v23i2a3159